HUGHES, H-D5020 EYE-FACE WASH - WALL MOUNTED STAINLESS STEEL 304
- Product Code: H-D5020 EYE-FACEWASH WITH STAINLESS STEEL BOWL
- Product SKU:
- Item Code: EWSH-SPS-D5020-1
- Availability: In Stock
H-D5020 - WALL MOUNTED EYE/FACE WASH (STAINLESS STEEL 304)
Made in UK
Approved by International Standards & Regulations
Open stainless steel bowl, wall-mounted emergency eye/face wash featuring twin spray nozzles protected by dust covers which lift off upon activation via the push plate.
The inbuilt flow regulator valve guarantees an optimum water flow. Comes with PP sign.
The eye wash diffusers are fitted with fine mesh strainers designed to give a gentle flow of aerated water at 12 litres per minute as per the ANSI standard.
This unit is intended for indoor use but can be located outdoors where there is no risk of overheating.
OPTIONAL EXTRA ATTACHMENT:
H-DA003 : GRP RED FOOT CONTROL PANEL ASSEMBLY FOR EYE/FACEWASH
H-D5020 - WALL MOUNTED STAINLESS STEEL 304 EYE/FACE WASH
HUGHES, INDOOR EYE FACE WASH STAINLESS STEEL
eyewash with stainless steel bowl
STAINLESS STEEL EYEWASH
STAINLESS STEEL EYEWASHER
Open stainless steel bowl, wall-mounted emergency eye/face wash featuring twin spray nozzles protected by dust covers which lift off upon activation via the push plate.
The flow regulator valve guarantees an optimum water flow.
The eye wash diffusers are fitted with fine mesh strainers designed to give a gentle flow of aerated water at 12 litres per minute as per the ANSI standard.
This unit is intended for indoor use but can be located outdoors where there is no risk of overheating or freezing.
Pedestal mounting options also available.
Emergency showers and eyewashes are required by the ANSI/ISEA Z358.1‐2014 standard to be
activated weekly, with a more thorough evaluation on an annual basis. With OSHA fine
increases of 80 percent having taken effect in August 2016, violations for inappropriate or
inadequate eyewash and shower equipment have resulted in penalties of more than $100,000.
The standard guides the placement, functionality, and maintenance requirements for
emergency showers and eyewashes. ANSI/ISEA Z358.1, in its current form, is the clearest and
most useful tool for protecting workers from eye, face, and bodily injuries resulting from caustic
and corrosive materials introduced by workplace incidents such as spills, splashes, and blown
particulates.
The standard requires stringent testing to be conducted on a regular basis to ensure properly
functioning equipment is being provided at all times if an incident were to occur. We should all
understand that compliance is not a once‐a‐year or once‐a‐month responsibility. Compliance is
an all‐day, every‐day requirement. Accordingly, emergency showers and eyewashes are
required by the ANSI/ISEA Z358.1‐2014 standard to be activated weekly, with a more thorough
evaluation on an annual basis. This requirement is established in Sections including 4.6.2, 4.6.5.
In practice, emergency response equipment such as eyewashes and showers sometimes fall to
the wayside when it comes to maintenance, especially when prioritized against emergency
preparedness equipment such as eye protection and fall protection. You should know that OSHA
does not prioritize or take a backseat when it comes to providing adequate and properly
functioning equipment, regardless whether the equipment aids pre‐ or post‐incident.
ANSI Weekly Minimum Performance Requirements
The standard itself has three minimum requirements for weekly inspections:
1. Emergency equipment shall be activated weekly. (Each piece of equipment is required to
be activated.)
2. Activation shall ensure flow of water to the head(s) of the device. (This would be both the
eyewash or eye/face wash head, as well as the showerhead.)
3. Duration of the activation shall be sufficient to ensure all stagnant water is flushed from
the unit itself and all sections of piping that do not form part of a constant circulation
system, also known as "dead leg" portions. (The duration is determined by the length of
piping where stagnant water could be sitting before it reaches the head(s) of the unit.)
In addition to the above weekly minimum performance checklist required by ANSI/ISEA, it
is recommended as a best practice to conduct additional weekly functional checks. The purpose
of these additional checks is to fully ensure the equipment is operating correctly and is capable
of providing proper first aid in the event of an emergency.